Heat recovery ventilation: Calculate heat savings and running costs

A ventilation system with heat recovery can transfer heat from the exhaust air to the fresh air. At the same time, the system uses electricity and requires maintenance. The calculator combines these factors in an estimate of the economics.

Applies to the amounts in this calculator.

cfm

Heating degree days in °F for a normal year, for example from your utility or NOAA.

°F·days

The documented temperature efficiency of the unit.

%
%
USD
kWh/year
USD/kWh
USD/year
USD

No connection. Your numbers have been kept. Please try again.

Worked example

  • Airflow: 58.8578 cfm
  • Heating degree days: 4,500 °F·days
  • Recovery: 80 %
  • Efficiency of the heating system: 90 %
  • Price per kWh of purchased energy: 0.15 USD
  • Extra electricity for fans: 400 kWh/year
  • Electricity price: 0.30 USD
  • Filters and service: 90.00 USD

Recovered heat

1,632 kWh per year

Ventilation loss without recovery 2,040 kWh · costs 210 USD · net 62 USD per year

A simplified model with heating degree days. Frost operation, bypass and air change rates are not assessed.

Compare with the same ventilation

A fair comparison starts from the same necessary air exchange. If the home was previously insufficiently ventilated, a low historical heat consumption is not automatically a suitable basis for comparison.

Enter the airflow, temperature conditions and documented heat recovery. Add the electricity use of the fans, filters and other running costs. A high laboratory value is not the same as the total annual saving. Frost protection, bypass and variation in heat demand can affect the result.

Guide to assessing a system

Use values from the specific quote

Find the airflow and electricity use at the relevant operating point. A system at maximum output does not necessarily describe normal operation in the home. Also find out what installation and later service cost.

Example of recovered heat

At 100 m³ of air per hour and a temperature difference of 20 degrees, the simplified ventilation loss is about 0.68 kWh in one hour. At 80 percent heat recovery, the recovered heat equals about 0.544 kWh before other system factors.

The economic value depends on your heat supply. So convert to avoided purchased energy, and subtract extra electricity and maintenance. The calculation does not assess the placement of the ducts, noise or moisture conditions. Those parts must be included in the planning of the specific system.